| Model | WHFP- | 34LM | 51LM | 68LM | 85LM | 102LM | 136LM | 170LM | 204LM |
|---|---|---|---|---|---|---|---|---|---|
| Air Flow (m³/h) | High | 340 | 510 | 680 | 850 | 1,020 | 1,360 | 1,700 | 2,040 |
| Medium | 260 | 390 | 510 | 640 | 770 | 1,020 | 1,280 | 1,530 | |
| Low | 170 | 260 | 340 | 430 | 510 | 680 | 850 | 1,020 | |
| Cooling Capacity (W) | H | 1.98 | 2.8 | 3.87 | 4.58 | 5.42 | 7.38 | 9.08 | 11.1 |
| Kcal/h | H | 1,702 | 2,408 | 3,328 | 3,938 | 4,661 | 6,346 | 7,808 | 9,546 |
| Rated heat | H | 3.39 | 4.5 | 6.35 | 7.45 | 9.22 | 12.4 | 16.3 | 19.5 |
| Kcal/h | H | 2,915 | 3,870 | 5,460 | 6,407 | 7,930 | 10,665 | 14,020 | 16,770 |
| The input power (W) | 12 Pa | 37 | 52 | 62 | 76 | 96 | 134 | 152 | 189 |
| 30 Pa | 44 | 59 | 72 | 87 | 108 | 156 | 174 | 212 | |
| 50 Pa | 49 | 66 | 84 | 100 | 118 | 174 | 210 | 250 | |
| The amount of water (Kg/h) | 350 | 510 | 660 | 800 | 980 | 1,280 | 1,600 | 1,920 | |
| Flow resistance (Kpa) | 30 | 30 | 30 | 30 | 40 | 40 | 40 | 40 | |
| Motor number | 1 | 2 | 3 | 4 | |||||
| Power | 220V/50HZ | ||||||||
Remarks:
1. Cooling testing condition return air dry ball/wet ball temperature 27℃/19.5℃ ,chilled water inlet temperature 7℃ , chilled water outlet temperature 12 ℃
2. Heating testing condition return air dry ball temperature 21 ℃ ,hot water inlet temperature 60℃,hot water outlet tempeature 50 ℃