Easy installation
Integration type (including water tank, water circulating pump, pressure pump, valves etc.) is available.
02
Best compressor equipped with intelligent control
Top brand scroll compressor brings high efficiency, high reliability, low noise, low vibration and compact size. By the application of the intelligent control, the system monitors the operating conditions of each compressor in running time and adjusts the operating time of each one in an intelligent and balanced way to prolong the lifetime of each unit.
03
Wide Operation Range
The EVI heat pump water heater can maintain stable and efficient performance in a wide ambient temperature from -25°C to 45°C, providing a wider range of applications for domestic & light commercial sanitary hot water heating.
04
Highest outlet water temp. 60C
Due to outlet water up to 60C, the unit can replace the traditional boilers which are applied to the house heating and domestic hot water.
05
Intelligent Control
HANHONG self-developed PCB can operate the heat pump unit in combination with other heat sources via Modbus RS485 meanwhile support various wired displays include LCD, LED, color touch display with significant functions like Fast Heating, Timer, PV-Ready and Remote upgradation etc..
| Product Model | LYKLNJ-7 | LYKLNJ-12 | LYKLNJ-15 | LYKLNJ-24 | LYKLNJ-30 | LYKLNJ-50 | LYKLNJ-60 | LYKLNJ-100 | |
|---|---|---|---|---|---|---|---|---|---|
| Cooling① | Rated Cooling Capacity (kw) | 18.9 | 32.5 | 42.5 | 65 | 85 | 130 | 170 | 260 |
| Rated Input Power (kw) | 6.3 | 10.7 | 13.5 | 21.5 | 27 | 42 | 54 | 94 | |
| EER | 3.00 | 3.04 | 3.15 | 3.02 | 3.15 | 3.10 | 3.15 | 2.77 | |
| Heating② | Rated Heating Capacity (kw) | 21.7 | 37.4 | 47.6 | 74.8 | 95 | 150 | 180 | 300 |
| Rated Input Power (kw) | 6.4 | 11 | 14 | 22 | 28 | 45 | 52.9 | 90 | |
| COP | 3.39 | 3.40 | 3.40 | 3.40 | 3.39 | 3.33 | 3.40 | 3.33 | |
| Heating③ | Heating Capacity (kw) | 14.5 | 24.9 | 31.2 | 49.9 | 62.4 | 104 | 124.8 | 208 |
| Rated Input Power (kw) | 5.6 | 9.6 | 12 | 19.2 | 24 | 40 | 48 | 80 | |
| EER | 2.59 | 2.59 | 2.60 | 2.60 | 2.60 | 2.60 | 2.60 | 2.60 | |
| Power Supply | 3N/380V/50HZ | ||||||||
| Refrigerant | R410A | ||||||||
| Condenser | Model | High-efficiency tank | |||||||
| Rated Cooling Water Flow (m³/h) | 3.4 | 5.8 | 7.8 | 11.7 | 15.5 | 25.8 | 30.96 | 51.6 | |
| Rated Heating Water Flow (m³/h) | 3.3 | 5.6 | 7.3 | 11.2 | 14.6 | 22.4 | 29.2 | 44.7 | |
| Water Inlet/Outlet Diameter (DN) | 32 | 40 | 40 | 50 | 65 | 65 | 80 | 100 | |
Remarks:
1. Rated Cooling Working Condition: Outdoor Air (DB/WB) 35°C/24°C; inlet water temperature 12°C, outlet water temperature 7°C.
2. Rated Heating Working Condition: Outdoor Air (DB/WB) 7°C/6°C; inlet water temperature 40°C, outlet water temperature 45°C.
3. Nominal Heating Working Condition: Outdoor Air (DB/WB) 7°C/6°C; inlet water temperature 30°C, outlet water temperature 35°C.