Commercial EVI DC Inverter heat pump
Heating & Cooling
R410a
Max. heating capacity: 238.7kw/h
- Features & Benefits
- Product Details
- Technical Specifications
- Installation
01
10Hz~120Hz Non-polar dc inverter technology
02
Brushless DC inverter fan
Fan motor speed increased 45% 35dB super silence
03
Working in ultra low temperature
Inverter compressor can run in ultra low temperature stably
04
Adaptive thermostat technology
Little temperature fluctuation, thermostat is more comfortable
05
Easy installation
The units can be easily transported module by module, and it can be installed on the building roof or outside without requirement for dedicated machine rooms or water towers.
01
DC Inverter Compressor
We select the world -famous brand Mitsubishi DC inverter compressor, which is well compatible with components inside the unit, and ensures the unit operates in an efficient way.
02
High Efficiency Evaporator
We use high efficiency heat exchanger, to make the system outlet water temperature reaches 60 degrees. There is no joint in the heat exchanger, which can reduce the hidden danger of the leakage of the refrigerant, which is clean and efficient.
03
High Efficiency Tube In Tube Heat Exchanger
We use high efficiency tube in tube heat exchanger. to make the system outlet water temperature reach 60 degrees,There are no joints in the heat exchanger, which can reduce the hidden dangers of the leakage of the refrigerant, With cleaning refrigerant, they system could work efficiently in a long term, which is clean and efficient.
04
High Efficiency In Energy Saving
The automatic water valve can induce the water temperature automatically, so as to achieve the requirements of independent control of water, water temperature is more accurate.
05
R410A Gas
Filled with environmental friendly R410a gas
06
Easy Maintenance Design
The unit uses the new Design driver board with integrated and compact design. This board is installed upside-down in the heat pump, which effectively helps to solve problems such as water ponding and dust accumulation. Only one screw needs to be taken down for maintenance.
| Product Model | LYKBLNJ-40 | LYKBLNJ-80 | LYKBLNJ-100 | ||
|---|---|---|---|---|---|
| 35℃ (Environment Temp.) | 7℃ (Outlet Water Temp.) | Rated Cooling Capacity (kw) | 84.6 | 172.8 | 216 |
| Rated Input Power (kw) | 32 | 64 | 80 | ||
| EER | 2.64 | 2.70 | 2.70 | ||
| 7℃ (Environment Temp.) | 45℃ (Outlet Water Temp.) | Rated Cooling Capacity (kw) | 95.5 | 191 | 238.7 |
| Rated Input Power (kw) | 28.1 | 56.2 | 70.2 | ||
| COP | 3.40 | 3.40 | 3.40 | ||
| -12℃ (Environment Temp.) | 41℃ (Outlet Water Temp.) | Heating Capacity (kw) | 73.1 | 146.2 | 182.3 |
| Rated Input Power (kw) | 28.1 | 56.2 | 70.2 | ||
| EER | 2.60 | 2.60 | 2.60 | ||
| Electric Parameter(V/PH/HZ) | 3N/380V/50HZ | ||||
| Max. Working Current (A) | 72 | 144 | 200 | ||
| Referigerant & Charge Volume | R410A/7500g*2 | R410A/7500g*4 | R410A/7500g*4 | ||
| Condenser | Model | High-efficiency tank | |||
| Rated Cooling Water Flow (m³/h) | 14.9 | 29.7 | 37.1 | ||
| Rated Heating Water Flow (m³/h) | 15.9 | 31.8 | 41.1 | ||
| Working Temperature (℃) | -35 ~ 45 | ||||
| Noise (db) | ≤56 | ||||
| Water Inlet/Outlet Diameter (DN) | 65 | 80 | 100 | ||
| Outline Dimension | Length (mm) | 1,270 | 2,400 | 2,400 | |
| Width (mm) | 1,270 | 1,300 | 2,600 | ||
| Height (mm) | 2,350 | ||||
| Net Weight (kg) | 800 | 1,500 | 2,000 | ||
Heating + Cooling Installation Diagram
Sample Project